Preparation
On Controller
- Boot the controller into Maintenance Mode.
- Set the security level to Management or Safety.
- Touch {System} > {Setup}.
- Select {Option Functions}.
- Cursor down to {MotoPlus Func} and set it to ENABLE.
- Cursor down to {Motoman Driver} and set it to ENABLE.
On PC
- Move the MotoPlus application executable (.out file) to a USB flash drive or SD card.
- Insert the USB flash drive or SD card into the programming pendant.
YRC1000/YRC1000micro Procedure
- Boot the controller into Maintenance Mode.
- Hold the [MAIN MENU] button while turning on the main power switch to the controller.
- Set the security level to Management or Safety.
- Select {DEVICE}.
- Select the storage media that is inserted that the MotoPlus application is stored on.
- Select {MotoPlus APL.} from the main menu.
- Select {LOAD (USER APPLICATION)}.
- Use the cursor to navigate to the application you want to load.
- Pressing the [SELECT] button will mark the application with a star.
- Press the [ENTER] button.
- Select {YES} to finish loading the selected application.
Troubleshooting
ERROR 3640 “Limit of file number” when loading the .out file.
- The maximum number MotoPlus files have already been loaded onto the controller. Touch {MotoPlus APL} > {Delete} to select and remove any unnecessary applications.
- If you wish to increase the limit, it is controlled by parameter S1D305. It is not recommended to increase this beyond a value of 3. However, there are limited occasions where more than 3 MotoPlus applications are required. In these cases, S1D305 may be increased to 5.
Note: When increasing S1D305, it is recommended to also increase S1D307 to 25.